ISO 14644-1:2015 sets cleanroom classes by the maximum number of airborne particles per cubic metre at given sizes. ISO Class 5 allows 3,520 particles of 0.5 µm and larger per m³; ISO Class 7 allows 352,000; ISO Class 8 allows 3,520,000. Each class step is a factor of ten. Other parts of the series cover monitoring, test methods, design and operation.
It gives pharmaceutical, hospital, laboratory and electronics users a measurable target for air cleanliness, which then drives HEPA filtration, air change rates, pressure cascades and gowning.
Practical note: a class is stated with its occupancy state: as-built, at-rest or operational. Pharmaceutical GMP grades map onto ISO classes but add their own limits, including microbiological ones. Agree the class and state with your quality team before design starts.