The challenge: every number is a specification
Pharmaceutical manufacturing, hospitals and laboratories all depend on air that meets a stated class and keeps meeting it. Cleanrooms are classified by particle count. Pressure differentials keep contamination flowing from clean to less clean. Humidity and temperature limits protect hygroscopic products and staff comfort in gowns. Compressed air that touches product or primary packaging must be dry, oil-controlled and free of viable organisms.
In Cambodia the climate makes each of these harder. Outdoor air is hot and humid for most of the year. Air handling units therefore carry a large latent load, and cooling coils alone may not hold low humidity in critical rooms. Compressor rooms run hot. Power interruptions can drop air handling units and collapse a pressure cascade within seconds. A design that works on paper in a temperate climate can fail its first humid season.
The second challenge is evidence. A room that met its class at handover but drifted since is a finding waiting to happen. Monitoring, maintenance and records are as much a part of the system as the hardware.
The air services pharma and healthcare need
Cleanroom air and the pressure cascade
The core is the air handling: an AHU with staged pre-filters, cooling and reheat, then terminal HEPA filters in the room. We size airflow to the ISO 14644 class and the heat and particle load. The positive-pressure cascade is set door by door, laminar flow units go over critical operations, and pass boxes move materials without breaking the cascade. Read clean rooms and positive pressure basics and see air quality and emissions.
Humidity and temperature
Low-humidity rooms for powders, capsules and effervescent products often need a desiccant rotor dehumidifier alongside the cooling coil, because a coil can only dry air to near its own surface temperature. We size the latent load from the tropical design condition, not an average day. See dehumidifiers, humidity control and our article on humidity control in pharmaceutical and food production.
Compressed air to a written class
Tablet coating, fluid-bed processing, blister packing and vial handling use compressed air. Each use point gets an ISO 8573-1 class from your risk assessment. To meet it, we specify oil-free or properly filtered generation, a desiccant dryer where a low pressure dew point is needed, and sterile-grade point-of-use filters. Distribution pipework is chosen to stay clean. See compressed air systems and air treatment.
Nitrogen
Nitrogen blankets solvents and sensitive liquids, inerts reactors and flushes packs. A PSA generator delivers the purity you specify, with an analyser and alarm. See nitrogen generators.
Cooling and monitoring
Chillers carry the HVAC and process loads, with N+1 where a room cannot be allowed to drift. A monitoring system records differential pressure, temperature, humidity, particle counts and compressed-air dew point, with alarms and history. See SCADA and monitoring.
Power and resilience
Air handling for graded rooms should restart in a defined sequence after a power cut, so the cascade is re-established before doors open. Standby chillers, backed-up power for monitoring and controls, and alarm logic that tells a door opening from a fan failure are design decisions, not afterthoughts. We write them into the control philosophy and test them at site acceptance.
A cleanroom is only as good as its worst humid afternoon and its last power cut.
Standards that apply
For compressed air, ISO 8573-1:2010 sets the purity classes and ISO 8573-7 the method for testing viable micro-organisms. HEPA filters are classified under EN 1822 and ISO 29463. The filters that protect them are classified under ISO 16890, which replaced EN 779.
Typical scope
| Package | What it usually includes |
|---|---|
| User requirements | Room list, classes, cascade, humidity and temperature limits, air use points |
| Air handling | AHUs, staged filtration, HEPA terminals, laminar flow units, pass boxes |
| Climate | Cooling, reheat, desiccant dehumidification, chillers with standby |
| Compressed air and nitrogen | Generation, dryers, sterile filtration, PSA nitrogen |
| Monitoring | Differential pressure, temperature, humidity, particle and dew-point alarms |
| Handover | FAT and SAT records, test results, as-builts, maintenance plan |
Our design and engineering team writes the specification with you. Installation and commissioning delivers the SAT records and documents your qualification needs. A maintenance contract keeps filter changes, calibrations and records on schedule.