Compressed Air Audit Checklist
Use this checklist to prepare for a compressed air assessment, whether you run it in-house or with Nexus Turnkey. It follows the supply, distribution and demand structure used by ISO 11011.
Before the audit: documents
- Single-line diagram and compressor-room layout
- List of compressors: make, model, kW, control type, age and hours
- Dryers, filters and receivers with ratings
- 12 months of electricity bills and the tariff structure
- Production schedule, including nights, weekends and holidays
- Known problems: low pressure, moisture, trips, noise, heat
Supply side
- Log kW (or amps and volts) on every compressor for at least a typical week
- Log discharge and header pressure
- Record load/unload behaviour and set points
- Check room temperature and ventilation at peak
- Check intake filters, coolers and condensate drains
Treatment and distribution
- Measure pressure drop across dryers and filters
- Measure pressure at the furthest and most critical users
- Check pressure dew point against the required ISO 8573-1 class
- Walk the ring main: dead ends, undersized drops, missing drains
- Ultrasonic leak survey with tagging and size estimates
Demand side
- List the users that set the required pressure
- Identify inappropriate uses (open blowing, cabinet cooling, sparging)
- Measure off-production demand (the 'leak load')
- Note planned changes and expansions
After the audit
- Baseline: kWh, delivered volume and specific energy (kWh/m³)
- Ranked actions with investment, assumptions and payback
- A measurement and verification plan for each action
- Responsibilities and dates