Activated carbon has a very large internal surface area on which gas molecules adsorb. It appears in two places on an industrial site. In compressed air, a carbon filter after a coalescing filter removes oil vapour and odour where the ISO 8573-1 oil class or taste and smell matter, as in food and pharmaceutical air. In exhaust and room air, carbon panels, units and adsorption towers capture VOCs and odours.
Carbon has a finite capacity. Once saturated it stops working, and the outlet concentration rises without any visible sign, so plan change-outs on calculated load, monitoring or breakthrough testing.
It is best suited to low or variable VOC loads. For large, continuous solvent loads a zeolite rotor with an oxidiser, or an RTO, is usually the better long-term choice. Keep carbon dry and away from liquid oil, which blocks pores.