A chiller runs a vapour-compression cycle, usually with scroll or screw compressors, and delivers chilled water to the loads. Air-cooled chillers reject heat directly to outside air through condenser coils; water-cooled chillers reject it to a condenser water loop and a cooling tower, which is generally more efficient but adds water treatment and tower maintenance.
Chillers are often among the largest electrical loads on a site. Efficiency is reported as COP, EER or kW per ton, and part-load metrics such as IPLV (AHRI 550/590) or SEER-type ratings say more about real operation than the full-load figure.
In hot climates, condenser conditions drive performance: dirty coils, recirculating hot air and poor tower water all raise energy use. Size for the real load profile, stage multiple units where demand varies, and log approach temperatures to catch fouling early.