One withdrawn standard, one current standard, one for HEPA
Air filter classes come from three standards. EN 779:2012 graded general ventilation filters G1 to F9, but it was withdrawn in 2018. Its replacement, ISO 16890, grades the same filters by how much particulate mass they capture in three size bands: ePM1, ePM2.5 and ePM10, with ISO Coarse for the rest. HEPA filters sit in a separate standard, EN 1822 (and ISO 29463), with H13 and H14 the classes most cleanrooms use.
Panel, pocket and HEPA are filter formats, not classes. A pocket filter can carry several different ratings. This article explains each standard, how to read a rating and how to specify filters that actually protect your process. It belongs to our industrial air quality guide.
EN 779:2012: what it measured, and why it went
EN 779 sorted filters into three groups:
- G1 to G4 (coarse), rated by average arrestance of a synthetic test dust.
- M5 and M6 (medium), rated by average efficiency on 0.4 µm particles.
- F7 to F9 (fine), rated the same way, with a minimum efficiency requirement added in the 2012 edition.
The weakness was the single particle size. Real air contains a spread of sizes, and the particles that matter most for health and for sensitive processes are often finer than 1 µm. ISO 16890 was published in 2016 to grade filters against the particle fractions used in air quality monitoring. EN 779 ran alongside it for a transition period of about 18 months and was withdrawn in mid-2018.
ISO 16890: reading ePM1, ePM2.5, ePM10 and ISO Coarse
ISO 16890 measures a filter’s efficiency across a range of particle sizes, then weights it by the particle mass distribution of typical outdoor air. The result is expressed against three fractions:
| Group | Particle size range | Qualifies when |
|---|---|---|
| ePM1 | 0.3 to 1 µm | At least 50% efficiency in that range |
| ePM2.5 | 0.3 to 2.5 µm | At least 50% efficiency in that range |
| ePM10 | 0.3 to 10 µm | At least 50% efficiency in that range |
| ISO Coarse | Larger particles | ePM10 efficiency below 50% |
A filter is classified in the finest group it qualifies for, and its efficiency is reported rounded down in 5% steps. So “ePM1 60%” means at least 60% of the mass of 0.3 to 1 µm particles is captured. ISO Coarse filters are rated instead by gravimetric arrestance, the share of test dust captured by weight.
One detail makes ISO 16890 more honest than its predecessor. Many synthetic media carry an electrostatic charge that boosts efficiency when new and fades in service. ISO 16890 tests the filter both as delivered and after a conditioning step that removes that charge, and uses the average. A filter that only performs while charged no longer looks better than it is.
Specify the particle fraction you need to stop, then buy the filter whose test report proves it.
HEPA: EN 1822 and ISO 29463
HEPA and ULPA filters are tested differently. Each filter is scanned at its most penetrating particle size (MPPS), the size it is least able to stop, which typically falls around 0.1 to 0.2 µm. EN 1822 groups them as:
- E10 to E12: efficient particulate air (EPA) filters.
- H13 and H14: HEPA. H13 requires at least 99.95% integral efficiency at MPPS; H14 requires at least 99.995%.
- U15 to U17: ULPA, for the most demanding cleanrooms.
ISO 29463 is the international counterpart and uses its own labels, such as ISO 35 H and ISO 45 H for the H13 and H14 levels. Cleanroom HEPA filters are normally leak-tested after installation as well, because a perfect filter in a poorly sealed frame still lets dirty air past. Our article on clean rooms and positive pressure covers how HEPA fits a pressure cascade and an ISO 14644 classification.
Panel, pocket and HEPA: format follows duty
| Format | Typical use | Notes |
|---|---|---|
| Panel filter | Pre-filter, coarse protection, inlet louvres | Low cost, flat or pleated; washable metal and nylon mesh types for grease or lint |
| Pocket (bag) filter | Main filter in an AHU | Large media area in a deep frame; available across ePM ranges |
| Rigid compact filter | Main or final filter where space is tight | Higher class in a shallow housing |
| Activated carbon filter | Odour and gas removal | Targets gases, not particles; pair with particle filters |
| HEPA | Final filter for cleanrooms and critical areas | Needs good pre-filtration to reach a sensible service life |
Filters work as a train. A coarse pre-filter protects a pocket filter, which in turn protects any HEPA stage. Getting the staging right is the cheapest way to extend the life of the most expensive filter in the AHU.
Tropical conditions and filter selection
Two features of Cambodian sites are worth designing for.
Dust and lint. Dry-season road dust, construction dust and, in garment plants, cotton lint load filters fast. A well-chosen coarse stage takes most of that load and keeps the fine filters working longer.
Humidity. Wet-season air is often near saturation. Some media and frames handle moisture better than others, and wet filters can grow microbes. Select media rated for high humidity, drain AHU sections properly and keep pre-filters upstream of cooling coils where the design allows.
Change filters on measured pressure drop, not the calendar. A simple differential pressure gauge across each stage shows when a filter has reached its final resistance. Higher pressure drop means more fan energy. Savings are project-specific. We measure them against a baseline and verify them after implementation; we don’t promise a blanket percentage.
Reading a filter data sheet
The class is only the start. A useful data sheet also gives:
- Rated airflow for the stated size. Efficiency and pressure drop are tested at this flow.
- Initial pressure drop at rated airflow. Lower means less fan energy from day one.
- Recommended final pressure drop, the point at which the filter should be changed.
- Dust holding capacity or test dust loading, which indicates service life.
- Fire and humidity behaviour of the media and frame, where relevant.
Compare filters at the same airflow. A filter that looks cheaper may simply have less media, a higher pressure drop and a shorter life.
A short specification checklist
- What you are protecting: people, product, a process or a downstream filter
- The particle fraction that matters: PM1, PM2.5, PM10 or coarse
- The required ISO 16890 class for each stage, or EN 1822 class for HEPA
- Airflow per filter and the initial and final pressure drop allowed
- Humidity, temperature and any oil mist, lint or chemical exposure
- Frame size and seal type for the existing housing
- The supplier's ISO 16890 or EN 1822 test report for the exact product
The system selector gives a first view of which filter train suits your application. For pharmaceutical and hospital duties, our pharmaceutical and healthcare page sets out the wider air requirements.
Replace the old labels with a proper specification
If your plant still orders filters as “F7” or “G4”, that is the moment to re-specify. We review the existing filter train, propose ISO 16890 and EN 1822 classes for each stage, and supply panel, pocket, carbon and HEPA filters from our filters and media range. Where a cleanroom or emissions system depends on them, we size the whole train with the air quality and emissions equipment it serves.