Protect the building around the pool
An indoor pool evaporates water continuously into a warm hall. If that moisture is not removed, it condenses on the coldest surfaces: windows, roof structure, ceiling voids and walls. The result is dripping glass, mould, corroded steelwork and an uncomfortable, clammy hall. A pool dehumidifier removes the moisture as it is released and is built to survive the warm, chlorinated air it works in.
AirMax swimming pool dehumidifiers are designed for this duty. Capacities are selected to your load. Ask for a datasheet.
How it works
Hall air is drawn through a filter and across a cold evaporator coil, where moisture condenses below its dew point and drains away. The heat removed in condensing that moisture is returned to the air over the condenser, so the energy that evaporated the water is recovered into the hall. Coils and casings are protected against corrosion from chlorinated air. Units are wall-mounted in the hall, installed through the wall from a plant room, or ducted for larger halls.
Where it fits
- Hotel and resort indoor pools.
- Sports centres, schools and club pools.
- Spa, hydrotherapy and wellness pools.
- Residential indoor pools.
Selection notes
- Evaporation sets the load. Pool area, water temperature, hall temperature and humidity, and how many people use the pool all change the evaporation rate. We calculate it from the design conditions, not from pool area alone.
- Pool covers. Covering the pool outside opening hours reduces evaporation and the load on the dehumidifier.
- Surface temperatures. In air-conditioned or shaded halls, cold surfaces such as glazing and ductwork can sit below the hall’s dew point. Air distribution should sweep them with dry air.
- Corrosion. Specify corrosion protection on the unit and on ducts and fixings in the hall.
- Fresh air. Pool halls also need ventilation for air quality. In a humid climate, that fresh air adds moisture and must be part of the calculation.
What Nexus provides
As technology partner and authorised distributor for AirMax, we calculate the evaporation load, select the unit and configuration, design air distribution and controls, install and commission the system, and maintain it with corrosion checks, filter and coil cleaning and spare parts.