Base load is the part of the demand profile that is always there while the plant runs. A base-load compressor is one assigned to carry it, ideally running fully loaded, where a fixed-speed machine is at its most efficient.
Splitting demand into base, variable and peak lets you size each machine for its job. Base-load units run near 100% load. A trim compressor, often a VSD, follows the variation. Standby covers maintenance and failure.
Practical note: base load is a measured figure, not an estimate from the nameplates. Log flow or compressor power over normal production, weekends and night shifts. Off-production demand, often mostly leaks, frequently turns out to be a larger share of base load than anyone expected.