In a well-run compressor hall, base-load machines run flat out and a single trim compressor absorbs the swings in demand. A variable speed machine is the usual choice for trim, because it can match output to demand without unloading.
The trim machine’s size matters. If its turndown range is smaller than the step between base-load machines, there will be control gaps where the system falls back to load/unload cycling.
Practical note: a sequencer should keep only one machine trimming at a time. Two VSDs fighting each other, or a VSD trimming alongside a part-loaded fixed-speed machine, wastes much of the drive’s benefit.