A sequencer coordinates several compressors as one system. Instead of each machine reacting to its own pressure switch, with staggered set points that push header pressure up, the sequencer reads one system pressure and starts, loads, unloads and stops machines in a planned order.
The result is a narrower pressure band, fewer machines part-loaded, less unloaded running and even running hours across the fleet. It also lets one trim compressor do the variable work.
Practical note: a sequencer works with each compressor’s own controller, which keeps its protections. In mixed-brand or older halls, integration is usually through a PLC or gateway using each machine’s available signals. That route also feeds data to SCADA.