Nearly all the electricity an air compressor draws ends up as heat. The US Department of Energy estimates that as much as 80-93% of the electrical energy used by an industrial air compressor is converted into heat, and that a properly designed heat recovery unit can recover roughly 50-90% of that available thermal energy.
On an oil-injected screw compressor the most useful heat is in the oil circuit, which a plate heat exchanger can transfer to water. On air-cooled machines, warm cooling air can be ducted to drying or space-heating duties.
In a tropical plant there is rarely demand for space heating, so the case rests on hot water: boiler feed preheat, washing, process or canteen use. Recovery only pays when the heat demand coincides with compressor running hours, so match the two before you invest, and keep a cooling path for when the heat is not needed.