Control moisture where the goods are
In a hot, humid climate, moisture damages fabric, finished garments and packaging long before anyone sees water. Mould grows on cotton and cartons, cartons lose stacking strength, metal trims tarnish, and goods arrive at the buyer smelling musty. The right dehumidifier for a garment factory or warehouse starts with a target relative humidity at the product, a sealed building envelope and a calculated moisture load. Then you choose the technology: refrigerant units for warm, humid stores, desiccant rotor units for lower dew points or cooler spaces, and controls that measure where the goods sit, not just at the door.
This article explains how moisture causes damage, how the two technologies compare and how to size and control a system. It is part of our industrial dehumidification guide.
What humidity does to garments and stores
Mould and odour. Mould needs sustained moisture at a surface. Building research such as IEA Annex 14 treats a monthly mean surface relative humidity above 80 percent as a mould risk. Cotton, cellulose cartons and paper tags all hold moisture and give mould something to feed on. Once spores take hold in a store, they spread.
Packaging failure. Corrugated cartons absorb moisture from humid air and lose compression strength. A carton stack that is stable in a dry month can lean or crush in a wet one.
Fabric behaviour. Natural fibres take up and release moisture with the surrounding air. Fabric that changes moisture content between cutting and sewing can change dimensions and handling.
Corrosion and staining. Metal zips, buttons, rivets and machine parts corrode faster in humid air, and corrosion products can stain fabric.
Rejected shipments. Mould, odour or damp packaging found at the destination can mean claims, rework or a rejected container, whatever the cause.
Humidity damage is done quietly, at the product, long before anyone sees water.
Relative humidity rises when air cools
Relative humidity is not a fixed property of the air. It depends on temperature. Air at a given moisture content has a lower relative humidity when warm and a higher one when cool. A warehouse that sits at an acceptable humidity in the afternoon can exceed it at night, as the building cools while the moisture stays.
The same physics explains condensation. Any surface colder than the air’s dew point collects water: a roof sheet at night, a concrete floor, goods brought out of an air-conditioned container. That is why the target should be set at the coldest point where goods are stored, and why measuring dew point alongside relative humidity is useful.
In Cambodia, outdoor air is warm and moist for much of the year, and the wet season makes it worse. Standard psychrometric tables put saturated air at 30 °C at about 30 g of water per m³. Every cubic metre of outdoor air that enters a store brings its share of that water with it.
Why air conditioning is not enough
An air conditioner removes some moisture as air passes over its cold coil. But its thermostat controls temperature. Once the room is cool enough, the compressor cycles off and moisture removal stops, while humid air keeps arriving. Over-cooling to force more dehumidification wastes energy and can drive relative humidity up in cooler corners. A dehumidifier controls moisture directly, and a combined system can control both temperature and humidity.
Refrigerant or desiccant
| Refrigerant (condensing) dehumidifier | Desiccant rotor dehumidifier | |
|---|---|---|
| How it works | Cools air below its dew point on a coil; water condenses and drains | A rotating wheel adsorbs moisture; a heated reactivation airstream drives it off |
| Works best | Warm, humid spaces at normal room temperature | Lower temperatures, low dew-point targets, large volumes of humid make-up air |
| Energy | Electricity for the refrigeration circuit; releases some heat into the space | Reactivation heat plus fans; the dry air leaves warmer |
| Typical role | Garment stores, finished-goods areas, general warehouses | Large or cool stores, very dry targets, treating fresh air before it enters |
Refrigerant units lose capacity as air temperature and dew point fall, because the coil can only remove water by getting colder than the air’s dew point. Desiccant units keep working at low temperatures and dew points. In a warm tropical warehouse, refrigerant units often carry the load. Where a very dry target or a large fresh-air volume is involved, a desiccant unit, sometimes followed by cooling, is the better tool. The AirMax dehumidifier range, which we supply as technology partner and authorised distributor, includes desiccant rotor units alongside other types. Ask us which units suit your space.
Size the moisture load, not the floor area
A dehumidifier is sized in kilograms of water removed per hour at the design condition, not by square metres. The load comes from several sources.
Moisture sources to account for
- Humid outdoor air entering through open doors and loading docks
- Infiltration through gaps in walls, roof edges and around shutters
- Ventilation or fresh air required for people
- People working in the space
- Wet processes nearby: washing, steam pressing, wet floors
- Moisture released by goods and packaging as they arrive
- Worst-case outdoor conditions in the wet season
Seal before you size
The cheapest kilogram of water is the one that never gets in. Close gaps, fit dock seals and fast-acting or strip-curtain doors, and separate humid areas from dry stores. Steam pressing and washing add a lot of moisture locally. Extract it at source rather than asking a store dehumidifier to remove it.
Garment plants and warehouses differ
In a garment plant, the critical areas are usually the fabric store, the cutting room and the finished-goods store. Each may need a different target. In a high-bay warehouse, check stratification: warm, humid air can collect under the roof while the floor is cooler. Air distribution matters as much as dehumidifier capacity.
Control where the goods are
A dehumidifier controlled by a single sensor near the door controls the door. Place calibrated humidity and temperature sensors at product level, in the coldest and least ventilated zones. Log the data, so you can show buyers and auditors what conditions the goods were stored in. Set alarms for high humidity and for a dehumidifier that stops.
The same applies to energy and avoided damage. Savings are project-specific. We measure them against a baseline and verify them after implementation; we don’t promise a blanket percentage.
Keep it running
A dehumidifier that stops quietly is worse than none, because everyone assumes the store is protected. A short maintenance routine keeps capacity where it was at commissioning:
- clean or change air filters, more often in dusty seasons;
- clean coils on refrigerant units, since dust on the fins cuts capacity;
- check condensate drains and pumps, especially before the wet season;
- inspect the rotor, seals and reactivation heater on desiccant units;
- recalibrate humidity sensors on a schedule, because drifting sensors control to the wrong number.
Getting the store under control
Start by measuring. A week of logged humidity and temperature at product level, in a wet-season month, shows how far conditions are from the target and when the problem peaks. From there, the moisture load, envelope fixes and equipment choice follow.
Our humidity control work covers the full chain, from measurement to design, industrial dehumidifiers, installation and monitoring. For sector context, see our pages on garment and textile plants and warehousing and logistics. Use the system selector for a first view, then send us your store dimensions and target and an engineer will size the load.