Humidity Control in Pharmaceutical and Food Production

Humidity control for pharmaceutical and food production: why moisture is a quality parameter, where limits come from, and how to design and monitor it.

Nexus Turnkey Engineering Team6 min read

Humidity is a quality parameter, not a comfort setting

In pharmaceutical and food production, humidity changes the product. Hygroscopic powders cake and stop flowing, tablets and capsules change hardness and disintegration, coatings dry unevenly, and condensation over open product is a contamination risk. Effective humidity control in a pharmaceutical or food plant starts with a limit defined by the product and process. It then needs an air system that can hold that limit under the worst outdoor conditions, usually dehumidification integrated with the air-handling unit, and continuous, calibrated monitoring with records your quality system can rely on.

This article explains why moisture matters, where limits come from and how the engineering fits together. It is part of our industrial dehumidification guide.

Why the climate makes this hard

Cambodia’s climate is among the most demanding for moisture-sensitive production. The World Health Organization’s stability-testing guidance (TRS 953, Annex 2, with its updated table of conditions) lists 30 °C and 75 percent relative humidity as the long-term stability testing condition for Cambodia, the condition used for the hottest and most humid climatic zone. That condition exists because products in this region must survive it.

For a production room, it means humid outdoor air is the main moisture load. Standard psychrometric tables put saturated air at 30 °C at about 30 g of water per m³. Every cubic metre of fresh air brought in for ventilation and pressurisation carries water that has to be removed before it reaches the product.

Where moisture affects product

AreaWhat moisture doesTypical control approach
Pharma: dispensing and granulationHygroscopic materials absorb water and change flow and weighing accuracyLow, stable humidity in the room; dehumidified supply air
Pharma: compression and encapsulationTablet hardness, sticking, capsule shell brittleness or softeningHumidity held within a validated band
Pharma: coating and dryingDrying rate and finish depend on the moisture in process airDehumidified process air at a controlled dew point
Food: powders, sugar, spices, instant drinksCaking, lumping, loss of flow, shorter shelf lifeLow-humidity filling and packing rooms
Food: confectionery and snacksStickiness, loss of crispness, bloomControlled humidity in production and packing
Food: chilled areasCondensation on cold surfaces, dripping over open productDew point kept below the coldest surface temperature

The limit for each area comes from the product, not from a general table. In pharmaceutical production, it is set by your quality team from material properties, product development data and validation. In food production, it comes from the product specification and the hazard analysis. Our role is to design a system that holds that limit with margin.

The limit comes from the product. The engineering has to hold it on the most humid day of the year.

Dew point is the number to control

Relative humidity depends on temperature. The same air has a lower relative humidity in a warm room and a higher one in a cool room. The dew point describes the actual moisture content, and it does not change with temperature. That makes it the better control variable when several rooms run at different temperatures, and the right number to compare with the coldest surface in a room. Any surface colder than the air’s dew point collects water.

How the air system achieves it

Cooling-based dehumidification

An air-handling unit dehumidifies by cooling air below its dew point on a coil, so water condenses and drains away. This works well for moderate targets. It has a floor: the coil surface cannot run much below freezing without frosting, so a cooling coil cannot deliver very low dew points. Over-cooling to remove moisture also means reheating the air afterwards, which costs energy.

Desiccant dehumidification

A desiccant rotor dehumidifier adsorbs water onto a slowly rotating wheel and releases it into a separate, heated reactivation airstream. It delivers low dew points that cooling alone cannot reach and keeps working when the air is cool. In pharmaceutical and food plants, a common arrangement is a cooling coil to remove the bulk of the moisture from humid outdoor air, a desiccant rotor to reach the target dew point, and a post-cooling coil to bring the air back to room temperature.

Integration with pressure and filtration

In a controlled area, the air system does several jobs at once. It filters, it maintains room pressure differentials so air flows from clean to less clean areas, and it controls temperature and humidity. A dehumidifier added without considering airflow and pressure can unbalance the cascade. Fresh-air volume set for pressurisation also sets much of the moisture load. Our article on clean rooms and positive pressure covers the pressure side.

Monitoring and records

Control without records is hard to defend in an audit. A sound monitoring arrangement includes the following.

Humidity monitoring in production areas

  • Calibrated temperature and humidity sensors at representative points, not only in the return duct
  • Dew point calculated or measured where rooms run at different temperatures
  • Continuous logging with time-stamped records
  • Alert and action limits set inside the validated or specified range
  • Alarms that reach someone who can act, out of hours too
  • A calibration schedule with records for every sensor
  • Data retained in line with your quality system
  • A documented response for excursions

Commissioning should prove the system holds the limit under realistic load, and seasonal performance should be reviewed after the first wet season. That is when the moisture load peaks.

Why excursions happen

When a room drifts out of its humidity range, the cause is usually one of a short list:

  • doors held open, or airlocks used as corridors, letting humid air in;
  • fresh-air dampers or settings changed without checking the moisture load;
  • a reactivation heater or fan failure on a desiccant unit;
  • fouled coils or filters that reduce airflow and capacity;
  • a sensor drifting out of calibration, so the system controls to the wrong value;
  • the first weeks of the wet season, when outdoor moisture peaks above the design assumption.

Each one has a design or maintenance answer. Size equipment for worst-case outdoor conditions with margin. Alarm the reactivation circuit separately. Calibrate sensors on a schedule. And review door discipline as part of operator training, because no air system can keep up with a door that never closes.

Specifying the system

Bring these to the first engineering discussion:

  • the limits for each room, as temperature and relative humidity or dew point, with their source;
  • room sizes, heights, occupancy and process heat and moisture sources;
  • fresh-air and pressurisation requirements;
  • cleanliness class and pressure cascade, if applicable;
  • the coldest surfaces in each room, such as chilled equipment or cold stores;
  • monitoring and record-keeping requirements from your quality system.

From those, an engineer calculates the moisture load at worst-case outdoor conditions and chooses between cooling, desiccant or combined treatment. On energy, a well-designed system avoids needless over-cooling and reheat. Savings are project-specific. We measure them against a baseline and verify them after implementation; we don’t promise a blanket percentage.

Next steps

Our humidity control work covers load calculation, equipment selection, integration with the air-handling system, installation and commissioning. Equipment comes from our industrial dehumidifiers range and, for the air-handling side, our HVAC and chillers range. For sector context, see our pages on pharmaceutical and healthcare and food and beverage plants. The system selector gives a first view. Then send us your room limits and an engineer will check what holding them will take.

Nexus Turnkey Engineering Team

Written and reviewed by the engineers who design, install and maintain industrial air systems for Nexus Turnkey in Cambodia. Questions about this article? Ask us directly.

FAQ

Questions engineers ask us

What humidity should a pharmaceutical production room be kept at?

There is no single figure. The limit comes from the product and process: the moisture sensitivity of the materials, the process step and the evidence in your product file and validation. Your quality team sets the limit. The engineering task is to hold it reliably, with margin, under worst-case outdoor conditions.

Does ISO 14644 set humidity limits for cleanrooms?

No. ISO 14644-1 classifies cleanrooms by airborne particle concentration only. Temperature and humidity are specified separately, from the product, the process and operator comfort, and are controlled by the HVAC system that also maintains the cleanroom's air changes and pressure cascade.

Can a standard air-handling unit hold low humidity?

A cooling coil can dehumidify down to a dew point a few degrees above freezing, because the coil surface would frost below that. For lower dew points, or where the moisture load is large, a desiccant rotor dehumidifier is usually added to the air-handling system, often with cooling before and after it.

How should humidity be monitored in a GMP area?

With calibrated sensors at representative points, continuous logging, alarm limits set inside the validated range, and records that can be reviewed and audited. Sensors should be calibrated on a schedule and their data kept with the batch or environmental records your quality system requires.

Next step